A ton cools far more house in Minneapolis than in Miami, so no single rule of thumb can be right.

Short answer

About 520 square feet per ton in a mixed climate such as Washington DC or St Louis, for an average house with 8 ft ceilings, falling to about 380 in south Florida and rising to about 620 in Minnesota. So a 3 ton unit cools roughly 1,130 to 1,850 sq ft depending on climate, and a 2,000 sq ft house in a mixed climate needs about 4 tons. A Manual J calculation for the actual house is the figure to buy on.

Size the AC for your house

Square feet per ton by climate zone

One ton of air conditioning is 12,000 BTU per hour of cooling. How much floor that covers depends on how many BTU per square foot of heat the house gains, which is set mostly by climate and then by how well the house keeps heat out.

Square feet cooled per ton, 8 ft ceilings, average sun
ZoneExamplesWell sealedAverage houseLeaky, older
Zone 1, hot humidMiami, Key West, Honolulu400380340
Zone 2, hotHouston, Orlando, Phoenix, New Orleans440430400
Zone 3, warmAtlanta, Dallas, Los Angeles, Charlotte500480440
Zone 4, mixedWashington DC, Seattle, St Louis, Nashville550520480
Zone 5, coolChicago, Denver, Boston, Detroit600570520
Zone 6, coldMinneapolis, Burlington, Helena670620550
Zone 7, very coldDuluth, Grand Forks, International Falls750690600
Zone 8, subarcticFairbanks, Barrow800740670

Not sure of your zone? Look up where your county falls.

What each AC size covers

Square feet an average house with 8 ft ceilings, by unit size and climate zone
UnitZone 1Zone 2Zone 3Zone 4Zone 5Zone 6
1.5 ton (18,000 BTU)560640720780850920
2 ton (24,000 BTU)7508509601,0401,1401,230
2.5 ton (30,000 BTU)9401,0701,1901,3001,4201,540
3 ton (36,000 BTU)1,1301,2801,4301,5601,7001,850
3.5 ton (42,000 BTU)1,3201,4901,6701,8201,9902,150
4 ton (48,000 BTU)1,5101,7101,9102,0802,2702,460
5 ton (60,000 BTU)1,8802,1302,3902,5902,8403,080

What size AC for 1,500, 2,000 or 3,000 sq ft

Going the other way, from the house to the unit, the air conditioner size calculator rounds the load up to the next size central systems are sold in. The calculator stays within 15 percent of the load where it can, because an oversized unit cools the air before it has dried it.

Cooling load in tons, and the standard size it calls for, average house with 8 ft ceilings
HouseZone 2Zone 4Zone 6
1,000 sq ft2.3 t: 2.5 ton1.9 t: 2 ton1.6 t: 2 ton, over 15%
1,200 sq ft2.8 t: 3 ton2.3 t: 2.5 ton2 t: 2 ton
1,500 sq ft3.5 t: 4 ton2.9 t: 3 ton2.4 t: 2.5 ton
1,800 sq ft4.2 t: 4.5 ton3.5 t: 3.5 ton2.9 t: 3 ton
2,000 sq ft4.7 t: 5 ton3.9 t: 4 ton3.3 t: 3.5 ton
2,500 sq ft5.9 t: two systems4.8 t: 5 ton4.1 t: 4.5 ton
3,000 sq ft7 t: two systems5.8 t: two systems4.9 t: 5 ton

Residential central air conditioners top out at 5 tons, so a house whose load is above that is split into two systems, often one per floor. The sizing chart lists loads for every common house size in all eight zones.

Why "square feet per ton" misleads

The figure is an average, and every one of the things it averages over moves it a long way:

  • Climate. A ton covers about 380 sq ft in zone 1 and 620 in zone 6, so any single number is wrong for most of the country.
  • The house. In zone 4, a well-sealed house gets 550 sq ft per ton and a leaky one 480.
  • Ceiling height. The load follows the volume of air, not the floor. With 10 ft ceilings the zone 4 figure drops from 520 to 420.
  • Sun. Big west or south windows take it down to 450; heavy shade raises it to 580.
  • Rounding. Units come in half-ton steps. A 1,300 sq ft house in zone 4 has a load of 30,063 BTU, just over 2.5 tons, and the next size up is 20 percent over the load. That is the case where a Manual J pays for itself, by showing whether the smaller unit is enough.

Sizing by square feet and rounding up at every step is how houses end up with oversized units, and an oversized unit is the more expensive mistake: it short cycles, leaves the house clammy and wears the compressor. Why an oversized system is worse, not safer explains the mechanism, and what a Manual J measures explains how to ask for one. Use the tables here to check a quote, not to replace one.

Reading the size of the unit you have

The tonnage is usually coded in the outdoor unit's model number as thousands of BTU: a two-digit number such as 24, 30, 36, 42, 48 or 60 means 2, 2.5, 3, 3.5, 4 or 5 tons. If the house cools quickly but feels humid, that is a sign the unit may be oversized; if it ran all afternoon on the hottest days and still held temperature, that is what a correctly sized unit does.

Frequently asked questions

How many square feet does a 3 ton AC unit cool?
About 1,560 sq ft of an average house in a mixed climate (zone 4), from about 1,130 in south Florida to 1,850 in a cold northern climate, at 8 ft ceilings.
What size air conditioner do I need for 2,000 square feet?
About 4 tons in a mixed climate for an average house: the load is 3.9 tons. In a hot climate (zone 2) it is 4.7 tons of load, and in a cold one (zone 6) 3.3.
What size AC do I need for 1,500 square feet?
About 3 tons in a mixed climate (a load of 2.9 tons), 4 in a hot one and 2.5 in a cold one, for an average house with 8 ft ceilings.
How many square feet per ton of air conditioning?
About 520 in a mixed climate, 380 in the hottest and 620 in a cold climate, for an average house. A well-sealed house gets more per ton, a leaky one less.
How many square feet does a 2 ton AC cool?
About 1,040 sq ft in a mixed climate, from 750 in the hottest zone to 1,230 in a cold one.
How many square feet will a 5 ton AC cool?
About 2,590 sq ft in a mixed climate and 1,880 in south Florida. 5 tons is the largest residential central unit, so bigger houses use two systems.
Is 500 square feet per ton accurate?
For an average house in a warm to mixed climate it is close: the figure is 480 in zone 3 and 520 in zone 4. It oversizes in cold climates and undersizes in the hottest ones.
Is it better to oversize an AC unit?
No. An oversized unit reaches the thermostat setting before it has removed the moisture, so the house is cold and clammy, and the short cycles wear the compressor. Stay within about 15 percent of a calculated load.
How do I tell what tonnage my AC unit is?
Look for a two-digit number in the outdoor unit’s model number: 24 means 24,000 BTU or 2 tons, 36 means 3 tons, 60 means 5 tons.